Water-infusing Tightness Test for Vacuum System of Steam Turbines

Before water is infused, it shall be confirmed that the inner repair work of the condenser  is finished and the  vacuum meter under the infusing  water level has been removed, the temporary support has been installed for the condenser with supporting spring at the bottom in order  to prevent spring stress overload, and then water can be infused. The water level generally shall be at 100 mm under the gland sealing bore, the  infusing water will be chemical water or clarified  water.(js)