Requirement on Control Valve of Thermal Engineering Automatic Regulatory System

1.The maximum flow of control valve is 1.2 to 1.4 times the rated flow.

2.The control valve flow generally shall be less than 15% of the rated flow.

3.The variation flow of the control valve is less than 5% of the rated flow.

4.The zero stroke of the control valve shall be less than 10% of total stroke.

5.The saturation zone shall occur when the pressure is over 85%.