(High temperature and high pressure boiler)
Water samples | Project | Unit | Standard | Time (h) | Remarks |
Demineralized water | DD | us/cm | 0.2 | 2 | |
Silica | ug/L | 20 | 2 | ||
Water supply | Hardness | umol/L | ≤2.0 | 2 | |
Dissolved oxygen | ug/L | ≤7 | 2 | ||
PH value | 8.8~9.3 | 2 | |||
DD(H) | us/cm | ≤0.2 | 2 | ||
Iron | ug/L | ≤30 | | ||
copper | ug/L | ≤5 | |||
oil | mg/L | ≤0.3 | |||
Boiler water
| PH value | 9~10.5 | 2 | ||
Phosphate radical | mg/L | 2~10 | 2 | ||
The chloride ion | mg/L | ≤4 | 8 | ||
DD | us/cm | ≤150 | 2 | ||
silica | mg/L | ≤2 | 2 | ||
Steam | silica | ug/L | ≤20 | 2 | |
Sodium ions | ug/L | ≤10 | 2 | ||
iron | ug/L | ≤20 | laboratory Every week | ||
copper | ug/L | ≤5 | |||
Condensation water | Hardness | umol/L | ≤1.0 | 2 | |
Dissolved oxygen | ug/L | ≤50 | 2 | ||
DD(H) | us/cm | ≤0.3 | 2 | ||
Workshop Condensation water Backwater | Hardness | umol/L | ≤5.0 | 4 | |
DD | us/cm | ≤10 | 4 | ||
iron | ug/L | ≤50 | 4 |